Powerware 9315 UPS
Powerware 9315 UPS Power System

The Powerware 9315 UPS is essential for mission-critical applications such as data centers, server farms, and transportation facilities.

In your pursuit of maximum power quality and availability, the Powerware 9315 UPS power supply is the answer, and can be paralleled for both redundancy and capacity using patented Powerware Hot Sync UPS technology. In addition to offering surge protection and backup power, the Powerware 9315 UPS power system delivers full uninterruptible power protection against all nine common problems.

Powerware 9315 UPS Features and Benefits:

  • Delivers increased usable power capacity via optional 0.9 output power factor on the Powerware 9315 200-500 and 400-500 and 750 kVA
  • Serial and X-slot Communication Card enabled.
  • Provides flexible runtime options for your application
  • Isolates connected equipment from all incoming power problems to provide the highest degree of protection with online, double-conversion technology
  • Maintains and monitors battery health continuously with DC Expert; dynamically updates information on battery time remaining
  • Integrates seamlessly with generators by using an intelligent input filter
  • Reinforces system reliability by reducing points-of-failure by incorporating reduced component count with its innovative design
  • Starts up with the push of a button and displays UPS status information on its monitor panel
  • Incorporates connectivity products to fit various environments and applications
  • Keeps you informed by sending notification for power and UPS events that you select
  • Sends clear output signal using intelligent controls with digital signal processing (DSP)
  • Increases system reliability and ensures perfect output power by using true pulse width modulation (PWM) to enable the Insulated Gate Bipolar
  • Transistors (IGBT) to switch at their highest capacity
  • Eliminates system-level single point-of-failure with Powerware Hot Sync patented paralleling technology

Powerware 9315 500-600kVA UPS Technical Specifications:

Input Specifications
Voltage Range +10% to -15%
Frequency Range +/-5%
Surge Protection Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2
Power Factor 0.95 Typical at full load with input filter
Output Specifications
Voltage RegulationBetter than +/- 1%
Voltage THD Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
Transient Response Less than 5% for 100% load, step full recovery within 1 cycle
Frequency Regulation(Free Run) +/- 0.005 Hz
Frequency Sync Range+/- 0.5 Hz
Frequency Slew Rate1 Hz/sec.
Load Crest Ratio3:1
Safety (pending)UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed EN 50091-1
All Cabinets provide seismic mounting features, selectable DC ground fault detection capability
Environmental
Audible Noise <75 dBA at 1 meter
Ambient Operating Temperature 0C to 40C
Ambient Storage Temperature -20C to 70C
Altitude5000 ft. (1500 m) at 40C without derating
Relative Humidity 5-95% non-condensing
EMCMeet FCC Class A, EN 50091-2 (CISPR 22, Class A, Restricted Access)
Electrostatic DischargeWithstands 25kV without damage or disturbance to load

Powerware 9315 200-500kVA UPS Technical Specifications:

200-300kVA400-500kVA
Input Specifications
Frequency Range(60Hz) 57-64 Hz
(50Hz) 47-53 Hz
(60 Hz) 57-64 Hz
Surge ProtectionMeets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
Power Factor0.95 Typical at full load with input filter0.95 Typical at full load with input filter
Output Specifications
Voltage RegulationBetter than +/- 1%Better than +/- 1%
Voltage THDLess than 5% (100% nonlinear load); Less than 3% (100% linear load)Less than 5% (100% nonlinear load);
Less than 3% (100% linear load)
Transient ResponseLess than 5% for 100% load, step full recovery within 1 cycle (2.5 ms)Less than 5% for 100% load, step full recovery within 1 cycle
Frequency Regulation(Free Run) +/- 0.005 Hz(Free Run) +/- 0.005 Hz
Frequency Sync Range+/- 0.5 Hz+/- 0.5 Hz
Frequency Slew Rate1 Hz/sec.1 Hz/sec.
Load Crest Ratio3:13:1
Power Factor0.9 (Optional)
Battery
Battery TypeSealed, maintenance-free lead acidSealed, valve regulated lead acid
Recharge time10-12x discharge to 95% capacity10-12x discharge to 95% capacity
SafetyUL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features selectable DC ground fault detection capability
UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features selectable DC ground fault detection capability
Environmental
Audible Noise<65 dBA at 1 meter<72 dBA at 1 meter
Ambient Operating Temperature0C to 40C0C to 40C
Ambient Storage Temperature-20C to +70C-20C to +70C
Altitude5000 ft. (1500 m) without derating5000 ft. (1500 m) without derating
Relative Humidity5-95% non-condensing5-95% non-condensing
EMI Suppression/EMCMeet FCC Class A, Subpart J of Part 15 and
EN 50091 (CIPR22,ClassA)
Meet FCC Class A, Subpart J of Part 15 and
EN 50091-2 (CIPR22,ClassA)
Electrostatic DischargeWithstands 25 kV without damage or disturbance to loadWithstands 25kV without damage or disturbance to load

Model Selection Guide 500-600kVA

  9315-7509315-750/625
Input Voltage volts480600480600
Output Voltage volts480600480600
Input Voltage Range      
Minimum volts408510408510
Maximum volts528660528600
Input/Output FrequencyHz60606060
AC Input (with input filter)     
Nominal Ampsamps913730761609
Maximum Ampsamps1141913951751
Bypass Input     
 amps902722752601
AC Input (without input filter)     
Nominal Ampsamps902722752601
 10 minutes maxamps1128902940752
DC Link      
Nominal DC Voltage volts384384384384
Float Voltage volts432432432432
End of Discharge volts320320320320
Nominal Ampsamps1954955416281628
Physical Attributes (w/o batt.)      
Single Module RT Configurations      
Installed Weightlbs13200132001320013200
 Installed Widthin149149149149
 Multi module Configurations      
 Installed Weightlbs12600126001260012600
 Installed Widthin126 5/8126 5/8126 5/8126 5/8
System Efficiencies      
 100% Load%94949494
 75% Load%94949494
 50% Load%93939393
Full Load Heat Dissipation     
 BTU/Hr. (x1000) 130.8130.8109.0109.0
KCal/Hr. (x1000) 33.033.027.527.5
Inverter Efficiency (Full Load)%95959595

Model Selection Guide 200-300kVA

  9315-2009315-250
/200
9315-250 9315-225 9315-300
/225
9315-300
 200 kVA
/160 kW
 200 kVA
/160 kW
 250 kVA
/200 kW
 225 kVA
/180 kW
 225 kVA
/180 kW
 300 kVA
/240 kW
Input Voltage volts400400400208480480480600480600
Output Voltage volts400400400208208480480600480600
Input Voltage Range            
Minimum volts340340340177408408408510408510
Maximum volts440440440229528528528660528660
Input/Output FrequencyHz50/6050/6050/6060606060606060
AC Input (with input filter)           
Nominal Ampsamps254245318544245245245200326267
Maximum Ampsamps3173063976880306306306250408333
Bypass Inputamps290290360800360360360294480392
AC Input (without input filter)           
Nominal Ampsamps288288374640288288288236384314
 10 minutes maxamps360360360800360360360294480392
DC Link            
Nominal DC Voltage volts420420420480480480480480480480
Float Voltage volts473473473540540540540540540540
End of Discharge volts351351351401401401401401401401
Nominal Ampsamps457457571450450450450450600600
Physical Attributes (w/o batt.)            
 Installed Weightlbs3812417741776363386338634177667741776677
 Installed Widthin656565103656565936593
System Efficiencies            
 100% Load%92929191929292919291
 75% Load%92909091929292909291
 50% Load%92888990919191889289
Full Load Heat Dissipation           
 BTU/Hr. (x1000) 47.847.859.761.853.746.239.261.771.782.4
KCal/Hr. (x1000) 12.512.515.015.513.511.69.815.518.120.8
Inverter Efficiency (Full Load)%93939393929394939393

Model Selection Guide 400-500kVA

 9315-4009315-400/3009315-500 9315-500/400
 400 kVA/320 kW 300 kVA/240 kW 500 kVA/400 kW 400 kVA/320 kW
Input Voltage volts400400480480480208
Output Voltage volts400400480480208208
Input Voltage Range        
Minimum volts340340408408408177
Maximum volts440440528528528229
Input/Output FrequencyHz50/6050/6060606060
AC Input (with input filter)       
Nominal Ampsamps5083815564454451025
Maximum Ampsamps6354766405605601280
AC Input (without input filter)       
Nominal Ampsamps598448654523523N/A
 10 minutes maxamps747560800640640N/A
DC Link        
Nominal DC Voltage volts420420480480480480
Float Voltage volts473473540540540540
End of Discharge volts351351401401401401
Nominal Ampsamps9146861000800800800
Physical Attributes (w/o batt.)        
 Installed Weightlbs61006100610061001010014100
 Installed Widthin74747474123172
System Efficiencies        
 100% Load%949494929190
 75% Load%949494929190
 50% Load%949394919089
Full Load Heat Dissipation       
 BTU/Hr. (x1000) 69.852.387.2107.3107.3119.0
KCal/Hr. (x1000) 17.613.22224.127.130.0
Inverter Efficiency (Full Load)%95959592.592.592.5
   
 Powerware Three-Phase UPS System 
 
Eaton Powerware UPS AppliancePower RangeTopology 
Powerware BladeUPS
Powerware BladeUPS System expands power protection from 12 kW to 60 kW in a single industry-standard 19" rack.
180 to 265 Vac, 311 to 519 Vac Online, Double-conversion on DemandPowerware BladeUPS
 
   
 
   
 
 About 42U Contact Us Careers Copyright Privacy Policy Site Map
Follow us on:
 Follow 42u on Twitter Subscribe to 42U's channel on YouTube View 42u's profile on slideshare
Copyright © 2015 42U. All Rights Reserved
42U | Phone: 1-800-638-2638 | http://www.42u.com/


Powerware 9315 UPS / Powerware 9315 UPS Power Solutions